How Corrosion Occurs in the Fire Sprinkler System Riser

Posted by Geert Van Moorsel, P.E. on Sep 20, 2019 9:07:00 AM

Oxygen corrosion is the primary and predominant source of metal loss in wet pipe fire sprinkler systems. The most common location for this corrosion, and resultant leaks, is at the high points of the wet pipe system where trapped air accumulates. Pockets of trapped air act as reservoirs of corrosive oxygen, which will continue to dissolve into adjacent water and drive the corrosion reaction until all the oxygen is consumed.

However, there is another location on a wet pipe system that sees corrosion related failures that is not addressed as frequently: the system riser.

Sources of Corrosion on the Riser

Most system risers are completely vertical sections of pipe, along with necessary control valves and drain connections, so trapped air would not be expected to accumulate at this location. However, based on numerous pipe samples that have been submitted for analysis (most with pin hole leaks), oxygen corrosion was still found to be occurring at the system riser.

Based on the submitted samples, two primary sources of corrosion were found to be occurring: trapped air was accumulating beneath the riser check valve, and general oxygen corrosion was occurring in systems that see frequent high-volume flow of fresh water.

Trapped Air at Riser Check Valve

riser check valve - corrosion below clapperMany wet system risers include a check valve that maintains system pressure, even with fluctuations in the water supply pressure. However, it is common for the pressure in the overhead piping above the riser check valve to increase to a level above the supply pressure within the fire water delivery piping. This generally occurs because of temperature increases in the overhead piping associated with the heating of the day and air that is always warmer against the ceiling.


As a result of the difference in pressure above and below the riser check valve, the check valve shuts. Any trapped air in the supply water will migrate to the bottom side of the check valve and accumulate there. The presence of the trapped air will result in corrosion in the section of piping beneath the check valve.

condensate corrosion on underside of clapper

The simplest way of preventing corrosion due to air accumulation under the check valve is the installation of an automatic air vent on one of the ports typically included on the check valve. This vent would automatically eject any air that accumulates before corrosion has time to occur.

Piping that Experiences Frequent, High Volume Flow of Fresh Water

Another common point of failure is the bulk supply piping, including the riser, of systems that see frequent, high volume flow of fresh water. Examples include the following:

  • Systems that undergo frequent tenant modifications/remodels, such as in a shopping mall.
  • Bulk supply piping that feeds multiple buildings/systems on a campus.
  • Piping near the fire pump, which undergoes frequent flow testing.

oxygen corrosion of riser piping (internal)Dissolved oxygen in the source water, which constitutes a small fraction of the oxygen available for corrosion in a wet pipe system, can still result in cumulative corrosion in piping that sees frequent, high volume flow. The piping downstream of fire pumps experiences the highest frequency of leaks, suggesting that these pumps may act to entrain additional oxygen into the water.

The corrosion of the piping results in the formation of iron oxide deposits, which can result in Under-Deposit Oxygen Acceleration of corrosion rate and occlusion of the piping, resulting in a reduction of flow.

Weld Seam Corrosion

The point of failure on riser piping is often located at the weld seam. Because corrosion occurs on the entire inner surface of the pipe, the longitudinal weld seam is always exposed to a corrosive environment. Fire sprinkler piping is rarely heat-treated, resulting in preferential corrosion of the weld seam.

weld seam corrosion

For additional information on the corrosion typically seen in fire sprinkler risers, please download our free white paper, Fire Sprinkler Riser Corrosion, below.

Geert Van Moorsel, P.E.

Written by Geert Van Moorsel, P.E.

Analytical Services Manager